Toshiba 1600EP Film Camera User Manual


 
TOSHIBA
35
Display Screens (cont'd)
Data Setting Screen
The following screens show the setting procedure for setting the data variables. They are accessed
from the main 'data setting screens' (see page 32) when the key is pressed:
Returns to Data Setting
Screens (with new
value applied)
Shift
Select
This setting uses the remote switch to
place the unit to bypass mode.
This setting uses the remote switch to
shut the output of the unit off. While off,
the online LED will be flashing and the
LCD will display the message:
The remote switch connection is on the
rear terminal block at positions 11 and
12. The unit will transfer 2 secs. after
closing the remote switch and will return
to UPS mode 2 secs. after the switch
opens. Default setting is BYPASS
This setting selects the RS232 as the
communication port, SNMP is disabled.
This setting selects the SNMP as the
communication port, RS232 is disabled.
Default setting is RS232
AUTO RETRAN: NO
TO ACCEPT:SET
AUTO RETRAN: YES
TO ACCEPT:SET
Loops through both
possibilities
Cont’d from Auto Re-
transfer Data Settings
Screen page 32
AUTO RETRAN: YES
TO CHANGE: SELECT
AUTO RETRAN: NO
TO CHANGE:SELECT
Set to “Yes”, the unit will automatically
retransfer back to UPS mode after
transferring momentarily to bypass mode
to prevent a sag in the output due to an
instantaneous load change. If set to
“No”, the unit will attempt to ride out the
load change and the output voltage
could be decreased momentarily.
Default setting is NO.
Set
Monito
r
Shift
Select
+
Set
Monito
r
Shift
Select
+
REMOTE:SYSDWN
TO ACCEPT:SET
REMOTE:BYPASS
TO ACCEPT:SET
Loops through both
possibilities
Cont’d Remote Operation
Data Settings Screen page 32
REMOTE:BYPASS
TO CHANGE: SELECT
REMOTE:SYSDWN
TO CHANGE:SELECT
Returns to Data Setting
Screens (with new
value applied)
OUTPUT SHUTDOWN
REMOTE OFF
Set
Monito
r
Shift
Select
+
Set
Monito
r
Shift
Select
+
COMM MODE: SNMP
TO ACCEPT:SET
COMM MODE: RS232
TO ACCEPT:SET
Loops through both
possibilities
Cont’d from Comm Mode
Data Settings Screen page 32
COMM MODE: RS232
TO CHANGE: SELECT
COMM MODE: SNMP
TO CHANGE:SELECT
Returns to Data Setting
Screens (with new value
applied)
Set
Monito
r
Shift
Select
+
Set
Monito
r
Shift
Select
+
INI BATT TST: NO
TO ACCEPT:SET
INI BATT TST: YES
TO ACCEPT:SET
Loops through both
possibilities
Cont’d from Int Batt Tst
Data Settings Screen
page 32
INI BATT TST: YES
TO CHANGE: SELECT
INI BATT TST: NO
TO CHANGE:SELECT
Set to “YES”, the unit will perform a
battery test the first time the unit
transfers to On Line. If Auto Run (see
page 33) is set to YES then the battery
test will be done at power up.
Default setting is YES
Returns to Data Setting
Screens (with new value
applied)
Set
Monito
r
Shift
Select
+
Set
Monito
r
Shift
Select
+