UPS Protection System
System Protection Features
The following schematic shows the electrical locations of the protection devices on the
1600EP models.
System Protection Functions
The following charts show the built-in UPS system fault protection functions on all the
1600EP models.
Built-In UPS Fault Protection Functions
Protection Item
Output overvoltage Output undervoltage Output overload
LCD Message
Cause
Control malfunction;
chip error
Control malfunction;
wire disconnected
Overload;Short circuit at load
Operation
Mode After
Fault
Bypass operation;
Chopper and inverter are stopped
Inverter OL: Transfer to bypass;
inverter stopped
Bypass OL: inverter, chopper
and bypass stopped
Audible Alarm
Yes; continuous buzzer
See ‘Audible Alarm Functions’ on
page 24
Visible Alarm
Red Fault LED “on”
Inverter OL: no fault lamp
Bypass OL: fault lamp “on”
Relay Contact
Alarm
Faulty relay closed;
Bypass relay closed
Fault relay open;
Inverter OL: Bypass relay closed
Bypass OL: Bypass relay open
Auto-retransfer
No
Inverter OL: Yes if bypass is OK
Bypass OL: No
OUT-OV OUT-UV
OVER LOAD
Inverter
*Switches are
solid state
devices
Input
power
Surge
absorber
MCCB
Line Filter
Input
fuse
Re cti f i e r /
Chopper
Batteries
+
_
Bypass
*Stati c
switch
Isolation
Tr ans for mer
Ou tp u t
fuse
Line Filter
Output
power
Power flow
Input
Abnormal
Low Battery
Level
Overheating
Overvoltage/
Undervoltage
Current Limit
Overload
Overcurrent