Reference Manual
00809-0200-4708, Rev AA
Smart Wireless Gateway for SteamLogic OPC Server
January 2014
Smart Wireless Gateway for SteamLogic OPC Server
Note:
OPC Item's Quality is read from the SteamLogic's Monitor Status:
OPC
value
State
User interface
icon
Meaning
2 Noisy Transition state before going to fully blowthru
3 Blow Thru
Steam trap has failed in the open position. It may have a mechanical failure
causing it to stick open or could be installed improperly.
4
No Data
Available
There are three reasons for this status;
1. The device has recently been configured and the state has not
been determined yet
2. The gateway has lost communication with the device so the
state cannot be confirmed
3. The device has a fault/error causing the state to be
undeterminable
5
Device Not
Configured
The device has been discovered, but has not been configured with the
required settings. Edit the trap details to configure the device.
6 Out of Service
Use the out of service feature in the device edit tab when a steam trap has a
scheduled period of down time to eliminate presenting the trap as cold. Out
of Service overrides all other trap states.
OPC
value
State
User
interface
icon
Meaning
Good Good The device is operating normally and reporting live information
Bad Bad Device malfunction. Use AMS, 475 handheld, or other HART tool to troubleshoot