3.0 INSTALLATION
Save the shipping carton and plastic packing in case the unit has to be returned for
credit or repair.
3.1 CONDUCTOR AND CABLE REQUIREMENTS
A minimum of 11 conductors plus coax is required, which includes common re-
quirements for motorized zoom lens and camera AC power.
Non-PP Models
11 Conductor 12 Conductor*
18 Awg 227 ft (82m) 494 ft (150 m)
16 Awg 432 ft (131 m) 785 ft (239 m)
14 Awg 690 ft (210 m) 1,253 ft (381 m)
PP Models
17 Conductor 18 Conductor*
18 Awg 227 ft (82m) 494 ft (150 m)
16 Awg 432 ft (131 m) 785 ft (239 m)
14 Awg 690 ft (210 m) 1,253 ft (381 m)
* Using 2 conductors for common
Calculations are based on a 10% cable loss with both motors running.
3.1.1 Recommended Mounts
MRWA Wall mount adapter
MRCA Ceiling mount adapter
3.1.2 Recommended Cables
C1906 Pretested 6-foot cable with video coax
C1925 Pretested 25-foot cable with video coax
NOTE:
The following are cable re-
quirements. A relay box (RB24) is
available to extend the operating dis-
tance up to 13,000 feet (3,962 m) over
16 Awg wire.