Pelco SW3 Security Camera User Manual


 
C2472M-A (12/05) 3
SW2–Termination Setting
When connecting more than one Spectra dome to a single controller, terminate the unit farthest from the controller. Termination is
only required for the last dome in the series.
The dome drive is shipped from the factory in the unterminated (OFF) position. To terminate the dome drive, set the SW2 switch to
the ON position.
NOTE: Coaxitron Control - Dome termination is not required.
SW3–Baud Settings
Pelco’s D-Type controllers are set for 2400 baud. The default setting for the dome drive is 2400 baud. If you are using a Pelco D-Type
controller, do not reset the SW3 switches.
P-Type controllers can operate at 2400, 4800, and 9600 baud. Set the SW3 switches (6, 7, and 8), located on the side of the dome
drive, to the same baud as the P-type controller.
Switch Number SW3-6 SW3-7 SW3-8
2400 Baud (default) Off Off Off
4800 Baud On Off Off
9600 Baud Off On Off
NOTE: Coaxitron Control - Configuring the baud setting is not required.
Special System Settings
AD-32 Preset System
SW3-1 should be set to the ON position if an AD-32 controller and Pelco’s TXB-AD translator board are used to control the dome
system.
CM9502 Setting
If a CM9502 matrix system is used with the dome drive, set SW3-2 to the ON position.