A SERVICE OF

logo

Specifications 35
UPS model VA Nominal power
rating (W)
Nominal voltage
setting
R1500 G3 INTL
1500
1000
220, 230, 240
Voltage specifications
Configuration setting (VAC) Available nominal output voltage (VAC)
100
100
110
110
120
120
220
220
230
230
240
240
Output tolerance specifications
Source of power Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating (within the
guidelines of the Computer Business Equipment
Manufacturers Association)
Battery power
±20% of nominal output voltage rating
Output feature specifications
Feature Specification
Online efficiency
95% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load
Surge suppression
ANSI C62.41 Category A (formerly IEEE 587)
Noise filtering
Full-time EMI/RFI filtering
Battery specifications
Feature Specification
Type
6 V, 9 AH, sealed, maintenance-free, valve-regulated,
rechargeable, lead-acid battery.
Voltage
The battery modules have a battery string voltage of 36 V.
Charging
Advanced charging for faster recovery. Complete charge takes at
least 48 hours. After approximately 24 hours, the batteries reach
90% charge at default nominal utility voltage and no load.
IMPORTANT: The 48-hour timer for the overall charge cycle triggers at the transition from charge
mode to float mode. For certain conditions such as heavily discharged batteries, battery
condition, and so on, it may take longer than usual to reach float mode. In these cases, it may take
longer than 48 hours to reach the rest mode.