![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/8/10/8100a917-830c-4cd3-85f3-6e7a31feb521/8100a917-830c-4cd3-85f3-6e7a31feb521-bg3.png)
ARI* CAPACITIES
COOLING CAPACITIES AND EFFICIENCIES
UNIT 582A NOMINAL TONS STANDARD CFM
NET COOLING
CAPACITIES (Btuh)
SEER†
SOUND RATINGS**
(Bels)
018040 1
1
/
2
600 18,000 10.0 7.5
024040
024060
2 800 24,600 10.0 7.5
030040
030060
2
1
/
2
1000 28,800 10.0 7.5
036060
036090
3 1200 34,400 10.0 8.0
042060
042090
3
1
/
2
1400 42,000 10.0 8.0
048090
048115
048130
4 1600 46,500 10.0 8.0
060090
060115
060130
5 2000 60,000 10.0 8.0
LEGEND
Bels – Sound Levels (1 bel = 10 decibels)
db – Dry Bulb
SEER – Seasonal Energy Efficiency Ratio
wb – Wet Bulb
*Air Conditioning & Refrigeration Institute.
†Rated in accordance with U.S. Government DOE (Department of
Energy) test procedures and/or ARI Standard 210/89.
**Tested in accordance with ARI Standard 270-89 (not listed inARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan
heat. Ratings are based on:
Cooling Standard: 80°F db, 67°F wb indoor entering-air tem-
perature and 95°F db outdoor entering-air temperature.
2. Beforepurchasing this appliance, read important energy cost and
efficiency information available from your retailer.
HEATING CAPACITIES AND EFFICIENCIES
UNIT 582A
HEATING INPUT
(Btuh)
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE RANGE (°F)
AFUE (%)
018040
024040
030040
40,000
31,000
31,000
31,000
20-50
79.9
80.1
80.1
024060
030060
036060
042060
60,000
46,000
46,000
46,000
47,000
35-65
35-65
25-55
25-55
78.4
78.4
78.7
78.7
036090
042090
048090
060090
90,000
71,000
71,000
70,000
70,000
40-70
79.9
79.9
78.6
78.6
048115
060115
048130
060130
LEGEND
AFUE – Annual Fuel Utilization Efficiency
NOTE: Before purchasing this appliance, read important energy cost
and efficiency information available from your retailer.
3
115,000
92,000
50-80
81.1
130,000
104,000
103,000
50-80 80.3