xviii SPARC Enterprise M4000/M5000 Servers Site Planning Guide April 2007
Caution – The CAUTION signal indicates a hazardous situation could result in minor or
moderate personal injury if the user does not perform the procedure correctly. This signal
also indicates that damage to the product or other property may occur if the user does not
perform the procedure correctly.
Task Warning
Normal
operation
Equipment damage
Be sure to follow the precautions below when installing the main unit. Otherwise,
the equipment may be damaged.
Do not block ventilation slits.
Avoid installing the equipment in a placed exposed to direct sunlight or near
equipment that becomes extremely hot.
Avoid installing the equipment in a dusty place or a place directly exposed to
corrosive gas or salty air.
Avoid installing the equipment in a placed exposed to strong vibration. Also,
install the equipment on a level surface so that it is stable.
The grounding wire must be class 3 or higher. Connecting it with another
grounding wire for shared grounding may cause a malfunction. Be sure to use
a single grounding path for the grounding wire.
Do not run any cable beneath any equipment. Also, prevent cables from
becoming taut. Never disconnect any power cable from the equipment while
power is being supplied to the equipment.
Do not place anything on top of the main unit. Do not use the main unit as a
workspace.
Avoid exposing the equipment to rapid changes in the ambient temperature,
such as a rapid increase during transport in winter. A rapid increase in the
ambient temperature causes moisture to condense in the equipment. Use the
equipment only after the difference between its temperature and the ambient
temperature is negligible.
Avoid installing the equipment near a copy machine, air conditioner, or
welding machine, which is noisy.
Take preventive action to minimize static electricity at the installation location.
Note that static electricity is easily generated in some carpets and can cause the
equipment to malfunction.
Confirm that the power supply voltage and frequency during operation match
the rated values indicated on the equipment.
Do not insert any object into an opening in the equipment. Components inside
the equipment use high voltage. Conductive foreign matter, such as a metal
object, inserted into the equipment, may cause a short circuit between
components, resulting in fire, electric shock, or equipment damage.