Fujitsu M4000 Security Camera User Manual


 
2-4 SPARC Enterprise M4000/M5000 Servers Site Planning Guide April 2007
Note – The power numbers in TABLE 2-2 are maximums and are based on fully
configured servers. Actual numbers might vary according to your server
configuration.
TABLE 2-2 Midrange Servers Electrical Specifications
SPARC Enterprise M4000 SPARC Enterprise M5000
Number of Power
Cords
2 (1 power cord per power supply unit) 4 (1 power cord per power supply unit)
Redundancy 1 + 1 redundant
Second power supply is redundant at 200
VAC
2 + 2 redundant
Second and fourth power supplies are
redundant at 200 VAC
Input voltage
100–127 VAC
200–240 VAC
100–127 VAC
200–240 VAC
Maximum current 24.0A at 100–127 VAC (12A/cord)
12.0A at 200–240 VAC (12A/cord)
48A at 100–127 VAC (12A/cord)
24A at 200–240 VAC (12A/cord)
Frequency 50–60 Hz 50–60 Hz
Power draw
(maximum)
2350W (2 power cords) 4590W (4 power cords)
Volt Ampere 2397 VA 4684 VA
Heat dissipation 8018 Btu/hr (8459 kJ/hr) 15661 Btu/hr (16523 kJ/hr)
Power factor
0.98 0.98
Connector type IEC 60320 C19 IEC 60320 C19
Plug type IEC 60320 C20
IEC 60309 16A 250V (All other locations
except Japan and Taiwan)
NEMA L5-15 125V 15A (Americas, Japan, and
Taiwan)
NEMA L6-20 250V 20A (Americas, Japan, and
Taiwan)
IEC 60320 C20
IEC 60309 16A 250V (All other locations
except Japan and Taiwan)
NEMA L5-15 125V 15A (Americas,
Japan, and Taiwan)
NEMA L6-20 250V 20A, Americas,
Japan, and Taiwan)