INSTALLING THE SUN SHROUD
The optional sun shroud fits over the top of the EH1512 enclosure. Perform the following steps to install the sun shroud.
1. Position the front of the sun shroud above the front of the enclosure.
2. Press the sun shroud down and against the enclosure until the sun shroud snaps into place.
Table B describes the minimum recommended cable sizes needed for use with the heater and blower combinations in the EH1512 enclosure.
Table A. Allowable Cable Diameter
Gland Cable Diameter
PG9 0.181-inch to 0.312-inch
PG11 0.230-inch to 0.395-inch
NOTE: Conduit must be used if the cable diameter
is greater than 0.395 inches (1.00 cm). RG11 coaxial
might be greater than 0.395 inches.
WARNING: When using a single power source for both camera and accessories, consider the camera power consumption when
determining the wire gauge. Table B does not include camera power.
Table B. Enclosure Accessory Wiring Distances
Model Number Input Voltage
Maximum Power
Consumption Cable Size Cable Distance
EH1512-1 120 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
2,782 ft (848 m)
4,424 ft (1,348 m)
7,035 ft (2,144 m)
11,184 ft (3,409 m)
EH1512-2 24 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
142 ft (43 m)
225 ft (69 m)
358 ft (109 m)
569 ft (173 m)
EH1512-3 230 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
6,473 ft (1,973 m)
10,291 ft (2,137 m)
16,365 ft (4,988 m)
26,019 ft (7,931 m)
EH1512-1MT,
EH1512-1MTS
120 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
2,782 ft (848 m)
4,424 ft (1,348 m)
7,035 ft (2,144 m)
11,184 ft (3,409 m)
EH1512-2MT,
EH1512-2MTS
24 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
142 ft (43 m)
225 ft (69 m)
358 ft (109 m)
569 ft (173 m)
EH1512-3MT,
EH1512-3MTS
230 VAC 22 W
20 AWG
18 AWG
16 AWG
14 AWG
6,473 ft (1,973 m)
10,291 ft (2,137 m)
16,365 ft (4,988 m)
26,019 ft (7,931 m)