Schneider Electric EM4800 Security Camera User Manual


 
PowerLogic
TM
EM4800 Series 930-112-01-B.00
PowerLogic configuration tool 01/2011
© 2011 Schneider Electric All Rights Reserved6
7. Assign the PC a static IP address such that the first three segments are
the same as the default IP address, and the last segment is different
from the default IP address. For example, 169.254.0.xxx, where xxx
differs from the last segment of the default IP address.
8. Configure the meter. See “Configuring the Meters” on page 7 for
configuration instructions.
9. Remove power. Use a properly rated voltage sensing device to confirm
power is off.
10. If you wish to lock the configuration parameters, remove the inner cover
and move the programming switches (SW1) to the OFF (up) position.
11. Re-install the inner cover.
12. Connect the LAN Etherent cable if present.
13. Re-install the outer cover.
14. Restore power.
NOTE: All PowerLogic EM4800 Series meters have a default IP
address of 169.254.0.10 in the absence of a DHCP service.
Network Connection Ethernet Requirements
To connect the PowerLogic EM4800 Series meter to the network:
1. Turn off power to the meter with the installed breaker or disconnecting
device. Use a properly rated voltage sensing device to confirm power
is off.
2. Remove the outer cover.
3. If you are changing parameters that require the programming switch to
be on, remove the inner cover and ensure the programming switches
are in the ON position.
4. Re-install the inner cover.
5. Using a CAT 5 Ethernet patch cable, connect the meter to a local
Ethernet switch.
6. Re-install the outer cover.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified
electrical personnel.
Turn off all power supplying this equipment before working on or
inside equipment.
Always use a properly rated voltage sensing device to confirm
power is off.
Replace all devices, doors and covers before turning on power to
this equipment.
The meters must be connected to the sense voltage and control
voltage through a properly rated disconnect.
Failure to follow these instructions will result in death or serious
injury.