Configuration and Use Manual 75
Configuring System Data Configuring APIConfiguring InputsConfiguring Security & Language
Chapter 9
Configuring the Petroleum Measurement
Application
9.1 About this chapter
This chapter explains how to configure the petroleum measurement application (API feature). The
petroleum measurement parameters include all the software parameters listed in Figure 9-1.
Note: The petroleum measurement application is an optional feature of the Series 3000 platform, and
may not be installed on your equipment. To verify that it is installed, use the View menu to list all
installed applications (see Section 17.5).
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.
9.2 API menu
Use the API menu, shown in Figure 9-1, to access and configure petroleum measurement parameters.
The API menu is a submenu of the Measurements menu, which is accessed through the Configuration
option of the Management menu. To access the Management menu, see Chapter 4.
Figure 9-1 API menu
Changing configuration can affect device operation.
Set control devices for manual operation before changing device configuration.
Measurements
API
•Table type
• User defined TEC
(1)
• Temperature units
(2)
• Density units
(2)
• Reference temperature
(3)
Density functions
See enhanced density manual
Discrete events
See Chapter 10
(1) Displayed only if Table Type is set to 6C, 24C, or 54C.
(2) Read-only.
(3) Read-only unless Table Type is set to 53x or 54x.