Pelco 27X Security Camera User Manual


 
50 C3463M (10/09)
ACTIVATE AUX
This setting activates an auxiliary when an alert condition exists. Settings include the following options:
NONE (default): Not activated.
1: An alert condition will close AUX 1.
2: An alert condition will close AUX 2.
CURRENT READING
The Current Reading menu displays the existing status of temperature, pressure, and dew point inside the dome system. An arrow displayed to
the left of a menu item denotes that an alert condition exists.
An up arrow indicates the reading is over the threshold. A down arrow indicates the reading is below the threshold.
The high temperature alert occurs if the temperature is above 140°F (60°C).
The low temperature alert occurs if the temperature is below -40°F (-40°C).
The high pressure alert occurs if the pressure is above 13 PSIG.
The low pressure alert occurs if the pressure is below 1 PSIG.
The dew point (high humidity) alert occurs if the difference between the temperature and the dew point is less than or equal to 3°C.
Note: The normal operating temperature inside the unit will be greater than the temperature outside the back box due to the heat emitted by the
system’s electronics.
RESET ALERT
Reset alert clears the alert condition and removes the alert label from the monitor. The system automatically checks internal conditions 60
seconds after reset. If conditions are still unacceptable, the alert label reappears on the screen indicating further corrective action is required.
TEMPERATURE
DEWPOINT
PRESSURE
REFRESH
BACK
EXIT
CURRENT READING