Toshiba 1600EP Film Camera User Manual


 
TOSHIBA
17
UPS Connections
Communication Interfaces (Cont'd)
RS-232C Interface Communication Specifications
The RS-232C serial communication specifications are shown below:
1) Communication system
2) Connection control system
3) Transmission speed
4) Synchronization method
5) Transmission code
6) Error detection
7) Error correction
8) Response monitoring
9) Transmission character format
10) Bit sending order
11) Frame length (information message)
Half-duplex communication system (serial
transmission)
Centralized control, polling/selecting system
1200/2400/4800/9600 baud
Start-stop synchronization
JIS X 0201,7bits (ANSI)
Vertical parity check, even (VRC)
longitudinal parity check, even (LRC)
None
None
10 bits
Low-order bits first
Variable length
RemotEye Network Card
The RemotEye is an optional network card for Toshiba UPS. This card slides into a slot located on
the back side (pages 45-46) of the UPS. The card provides a network, or LAN-based
communication interface for the UPS. When installed, the UPS can be managed remotely using the
common SNMP and HTTP (web-based) network protocols. The following diagram shows the flow of
the Network Management Station.
Note:
The UPS communication mode setting must be set to “SNMP” mode when using the RemotEye
network card (See Comm Mode variable in the 'Data Setting Screens' on page 32 and 34).
Network
Management
Station
Toshiba UPS
Network Communication through Ethernet