IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions
for 3.6, 6, 8, 10, 14, and 18 kVA that should
be followed during the installation and maintenance of the UPS and its batteries.
Hardwire type UPS units are not equipped with an over-current protection device nor an output
disconnect for the ac output. Therefore, a circuit breaker should be provided by the user between the
UPS output and the load input. This device should be rated as follows:
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA
240VAC
RATING
20A 30A 40A 60A 80A 125A
The maximum ambient temperature in which the UPS unit should be operated in is 104° F (40° C).
The nominal battery voltages for these models are as follows:
3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA
BATTERY
VOLTAGE
216Vdc 216Vdc 288Vdc 288Vdc 288Vdc 288Vdc
Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries. To arrange for battery replacement, contact your nearest Toshiba authorized service
center.
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the
use of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to
the eyes and skin and could also be toxic.
SAVE THESE INSTRUCTIONS