Temperature checkout
Proper cooling of the system is important for proper opera-
tion and system reliability. For a typical Netfinity server, you
should make sure:
Each of the drive bays has either a drive or a filler panel
installed
The top cover is in place during normal operation
There is at least 50 mm (2 inches) of ventilated space
at the sides of the server and 100 mm (4 inches) at the
rear of the server
The top cover is removed for no longer than 30 minutes
while the server is operating
Cables for optional adapters are routed according to
the instructions provided with the adapters (ensure that
cables are not restricting air flow)
The fans are operating correctly and the air flow is
good
A failed fan is replaced within 1 hour.