17
RT-PRC005-EN
General
Data
(6 - 10 Ton)
High Efficiency
Table GD - 4— General Data
6 Ton 7½ Ton 8½ Ton 10 Ton
Convertible Units Convertible Units Convertible Units Convertible Units
THC072A3, A4, AW THC092A3, A4, AW THC102A3, A4. AW THC120A3, A4, AW
Cooling Performance
1
Gross Cooling Capacity 73,000 94,000 103,000 117,000
EER
2
11.5
6
11.5
6
11.5
6
11.2
6
Nominal CFM / ARI Rated CFM 2,400/2,100 3,000/2,625 3,400/3,000 4,000/3,200
ARI Net Cooling Capacity 70,000 90,000
10
98,000
10
109,000
10
Integrated Part Load Value (IPLV)
3—
11.9
8
12.1
8
12.0
8
System Power (kW) 6.09
7
7.83
7
8.52
7
9.73
7
Compressor
No./Type 1/Climatuff Scroll 2/Climatuff Scrolls 2/Climatuff Scrolls 2/Climatuff Scrolls
Outdoor Sound Rating (dB)
4
89 91 89 88
Outdoor Coil — Type Lanced Lanced Lanced Lanced
Tube Size (in.) O.D. 0.3125 0.3125 0.3125 0.3125
Face Area (sq ft) 17.00 17.50 19.83 27.21
Rows/FPI 3/17 3/17 3/17 3/17
Indoor Coil — Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq ft) 9.89 12.36 12.36 12.36
Rows/FPI 3/16 3/16 4/16 5/16
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan — Type Propeller Propeller Propeller Propeller
No. Used/Diameter (in.) 1/26 1/26 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 6100 6200 6600 7000
No. Motors/HP 1/0.70 1/0.70 1/0.75 1/0.75
Motor RPM 1075 1075 1075 1075
Belt Drive Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1
Diameter x Width (in.) 12 x 12 15 x 15 15 x 15 15 x 15
Drive Type/No. Speeds Belt/Variable Speed Belt/Variable Speed Belt/Variable Speed Belt/Variable Speed
No. Motors 1 1 1 1
Motor HP (Standard/Oversized) 1.00/2.00 2.00/3.00 2.00/3.00 3.00/5.00
Motor RPM (Standard/Oversized) 1750 1750 1750 1750/3450
Motor Frame Size 56 56 56 56
Filters — Type Furnished
9
Throwaway Throwaway Throwaway Throwaway
(No.) Size Recommended (in.) (4) 16 x 25 x 2 (4) 20 x 25 x 2 (4) 20 x 25 x 2 (4) 20 x 25 x 2
Optional Hot Gas Reheat Coil — Type Lanced Lanced Lanced
Tube Size (in.) OD 0.375 0.375 0.375
Face Area (sq. ft.) 5.19 5.19 5.19
Rows/FPI 2/16 2/16 2/16
Refrigerant Charge (Lbs of R-22)
5
10.7 6.4 Circuit 1 7.4 Circuit 1 11.0 Circuit 1
6.2 Circuit 2 7.1 Circuit 2 7.3 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.
9. Optional 2” Pleated Filters also available.
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.