Table PD-52 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 707 0.35 774 0.42 837 0.50 898 0.57 953 0.65 1001 0.72 1045 0.80 1087 0.87 1129 0.95 1168 1.03
1800 778 0.48 840 0.56 897 0.64 953 0.72 1008 0.81 1058 0.89 1102 0.98 1143 1.06 1181 1.15 1219 1.23
2000 850 0.65 908 0.73 961 0.81 1012 0.90 1062 1.00 1111 1.09 1157 1.19 1198 1.28 1237 1.37 1274 1.47
2200 923 0.84 978 0.93 1028 1.02 1075 1.12 1120 1.22 1166 1.32 1211 1.43
2400 997 1.07 1049 1.17 1096 1.27 1140 1.37 1183 1.48 ———————
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
1600 1206 1.12 1241 1.20 1275 1.28 1306 1.37 1338 1.46
1800 1256 1.32 1291 1.41 1326 1.50
2000
2200
2400
Performance
Data
(5 Ton)
High Efficiency
Table PD-53— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1000 507 0.11 599 0.16 671 0.21 735 0.26 792 0.31 843 0.37 889 0.42 931 0.48 971 0.54 1007 0.59
1200 570 0.17 654 0.23 727 0.28 787 0.34 843 0.40 895 0.46 942 0.52 986 0.59 1026 0.66 1064 0.73
1400 638 0.25 711 0.31 782 0.38 844 0.44 896 0.51 946 0.58 993 0.65 1037 0.72 1078 0.79 1117 0.86
1600 707 0.35 774 0.42 837 0.50 898 0.57 953 0.65 1001 0.72 1045 0.80 1087 0.87 1129 0.95 1168 1.03
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Table PD-53 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1000 1042 0.65 1078 0.70 1110 0.76 1142 0.82 1175 0.89
1200 1099 0.80 1133 0.86 1166 0.93 1197 0.99 1227 1.06
1400 1153 0.94 1188 1.02 1221 1.10 1253 1.18 1284 1.27
1600 1206 1.12 1241 1.20 1275 1.28 1306 1.37 1338 1.46
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. BAYLSDR008A Required.
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
1-HP Standard Motor & Drive