Trane 13RT-PRC005-EN Film Camera User Manual


 
50 RT-PRC005-EN
(8½ Ton)
High Efficiency
Performance
Data
Table PD-60— Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 -- -- -- -- 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
3060 -- -- -- -- 626 0.68 665 0.78 703 0.90 740 1.04 775 1.17 810 1.30 843 1.44 875 1.58
3400 -- -- 628 0.72 669 0.84 706 0.96 741 1.08 775 1.21 809 1.36 841 1.51 873 1.65 904 1.81
3400 641 0.81 677 0.92 713 1.04 749 1.17 781 1.30 813 1.43 845 1.58 875 1.73 905 1.89 935 2.06
4080 693 1.03 726 1.15 758 1.27 792 1.41 824 1.56 854 1.69 883 1.83 912 1.99 940 2.16 968 2.33
2-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3060 905 1.73 933 1.89 960 2.05 986 2.20 1010 2.37 1035 2.54 1059 2.71 1083 2.89 1107 3.06 1131 3.24
3400 933 1.96 962 2.11 990 2.27 1016 2.44 1041 2.62 1065 2.79 1089 2.97 1112 3.15 1134 3.34 -- --
3400 964 2.22 992 2.39 1018 2.55 1045 2.72 1071 2.90 1095 3.08 1118 3.26 1141 3.45 -- -- -- --
4080 995 2.51 1023 2.69 1048 2.86 1075 3.05 1100 3.23 1124 3.41 -- -- -- -- -- -- -- --
3-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
1700 802 1.07 833 1.19 864 1.32 893 1.45 921 1.59 948 1.72 972 1.86 998 2.01 1022 2.15 1045 2.30
2040 823 1.21 854 1.34 884 1.47 913 1.60 940 1.73 967 1.87 993 2.01 1018 2.16 1043 2.32 1068 2.48
2380 846 1.37 876 1.51 906 1.65 934 1.79 962 1.93 988 2.08 1014 2.22 1038 2.37 1064 2.53 1087 2.69
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3-HP Oversize Motor & Drive
Table PD-61— Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW — Downflow Airflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive
Accessory Kit (1)
1700 481 0.26 533 0.35 578 0.44 621 0.54 661 0.64 700 0.74 736 0.85 770 0.96
2040 511 0.34 562 0.43 608 0.52 649 0.63 686 0.74 722 0.85 757 0.97 791 1.09
2380 496 0.33 545 0.42 592 0.52 637 0.63 678 0.74 716 0.86 751 0.98 784 1.11 815 1.24
2720 490 0.35 539 0.44 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2720 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009A Required.
2. BAYLSDR009A Required.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using
the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s
warranty will not be affected.
2-HP Standard Motor & Low Static
Drive Accessory Kit (2)
2-HP Standard Motor & Drive