Trane 13RT-PRC005-EN Film Camera User Manual


 
34 RT-PRC005-EN
Table PD-29— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 674 0.33 735 0.39 786 0.45 835 0.50 883 0.56 928 0.63 972 0.70 1011 0.77 1048 0.84 1084 0.90
1800 743 0.46 801 0.52 849 0.59 894 0.65 937 0.70 979 0.77 1021 0.85 1060 0.93 1098 1.01 1134 1.09
2000 813 0.61 866 0.68 914 0.76 956 0.83 995 0.89 1035 0.96 1073 1.02 1111 1.10 1147 1.19 1183 1.28
2200 886 0.80 933 0.87 980 0.96 1019 1.03 1057 1.11 1093 1.18 1129 1.25 1164 1.33 1198 1.40 1233 1.50
2400 959 1.03 1000 1.10 1045 1.19 1085 1.28 1121 1.36 1154 1.45 1188 1.53 1221 1.60
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
(5 Ton)
Standard Efficiency
Performance
Data
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-29 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1117 0.97 1150 1.04 1183 1.11 1215 1.18 1244 1.25
1800 1167 1.16 1199 1.24 1230 1.31 1259 1.39 1289 1.47
2000 1216 1.37 1249 1.47
2200
2400
Table PD-30 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 746 0.39 812 0.47 876 0.54 934 0.62 985 0.70 1032 0.77 1074 0.85 1117 0.93 1157 1.01 1196 1.09
1800 824 0.54 883 0.62 940 0.70 996 0.79 1048 0.88 1094 0.96 1137 1.05 1176 1.14 1214 1.22 1252 1.31
2000 902 0.72 957 0.80 1008 0.90 1059 0.99 1110 1.09 1157 1.19 1200 1.28 1239 1.38 1276 1.47 1311 1.50
2200 981 0.93 1032 1.03 1080 1.13 1126 1.23 1173 1.34 1219 1.44 ———————
2400 1061 1.19 1109 1.29 1153 1.40 1196 1.50 ———————
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-30 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1232 1.18 1267 1.26 1299 1.35 1332 1.45
1800 1289 1.41 1323 1.50
2000
2200
2400