RT-PRC005-EN
Performance
Data
(4 Ton)
High Efficiency
Table PD-46 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 626 0.23 686 0.27 744 0.32 796 0.38 843 0.43 885 0.49 927 0.54 967 0.60 1005 0.66
1440 609 0.24 674 0.30 730 0.34 783 0.39 834 0.45 882 0.52 924 0.58 964 0.64 1002 0.70 1038 0.76
1600 661 0.32 724 0.38 776 0.44 825 0.49 872 0.54 919 0.61 962 0.68 1002 0.75 1039 0.82 1076 0.89
1760 716 0.42 775 0.48 825 0.54 870 0.60 915 0.66 958 0.72 999 0.79 1040 0.87 1078 0.95 1113 1.03
1920 771 0.53 825 0.59 875 0.66 918 0.73 959 0.79 1000 0.86 1039 0.92 1078 1.00 1116 1.09 1151 1.17
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-46 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1041 0.72 1076 0.78 1110 0.84 1143 0.91 1176 0.98
1440 1074 0.83 1108 0.89 1141 0.96 1174 1.03 1205 1.10
1600 1109 0.95 1142 1.02 1175 1.09 1207 1.17 1236 1.24
1760 1147 1.10 1179 1.17 1211 1.25 1241 1.32
1920 1186 1.26 1218 1.34 1249 1.42
Table PD-47 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Downflow Airflow— Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
800 501 0.09 571 0.13 633 0.16 690 0.20 742 0.25 792 0.29 838 0.34 882 0.39 923 0.44
960 459 0.09 539 0.13 609 0.17 668 0.21 721 0.25 771 0.29 819 0.34 864 0.39 906 0.44 947 0.50
1120 509 0.13 580 0.17 646 0.21 706 0.26 758 0.31 805 0.36 850 0.41 893 0.46 934 0.51 973 0.57
1280 559 0.18 626 0.23 686 0.27 744 0.32 796 0.38 843 0.43 885 0.49 927 0.54 967 0.60 1005 0.66
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1280 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007A Required.
2. BAYLSDR007A Required.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-47 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
800 963 0.49 999 0.54 1034 0.59 1068 0.65 1101 0.70
960 986 0.55 1023 0.61 1060 0.67 1095 0.73 1127 0.79
1120 1012 0.63 1048 0.69 1084 0.75 1118 0.81 1151 0.88
1280 1041 0.72 1076 0.78 1110 0.84 1143 0.91 1176 0.98
1-HP Standard Motor &
Low Static Drive
Accessory Kit (1)
1-HP Standard Motor & Low Static Drive Accessory Kit (2)
1-HP Standard Motor & Drive