Raritan Computer DSX-0N-E Security Camera User Manual


 
162 DOMINION SX USER GUIDE
Pre-condition Administrator user is logged in via CLI.
6 Power Strip devices (DPX) are physically connected and configured to
DSX.
User is in power menu.
Action 1. Enter Command to associate Port1 to Outlet1 of PowerStr1.
2. Press Enter.
3. Repeat steps 1 and 2 to associate Port1 with Outlet1 from each of the
other PDUs.
CLI Input
associate port 1 powerstrip PowerStr1 outlet 1
associate port 1 powerstrip PowerStr2 outlet 1
associate port 1 powerstrip PowerStr3 outlet 1
associate port 1 powerstrip PowerStr4 outlet 1
associate port 1 powerstrip PowerStr5 outlet 1
associate port 1 powerstrip PowerStr6 outlet 1
Scenario #8 Port Power Association – Edit outlet names
Pre-condition Administrator user is logged in via CLI.
Power Strip device (DPX) is physically connected and configured to DSX
named PowerStr1.
User is in power menu.
Action 1. Enter Command to edit outlet1 name of PowerStr1.
2. Press Enter.
CLI Input outlet name PowerStr1 outlet 1 newname TestName
Remove Port Power Association
Description: Power Control Menu – Remove a power outlet association from a DSX port.
Scenario #1 Remove Port Power Association
Pre-condition Administrator user is logged in via CLI.
Power Strip device (DPX) is physically connected and configured to DSX
named PowerStr1.
User is in power menu.
Action 1. Enter command.
2. Press Enter.
CLI Input Command: unassociate port 1 powerstrip PowerStr1 outlet 1
Scenario #2 Delete multiple outlets Association
Pre-condition Administrator user is logged in via CLI.
Power Strip device (DPX) is physically connected and configured to the
DSX named PowerStr1.
User is in power menu.
Action 1. Enter command.
2. Press Enter.
CLI Input Command: unassociate port 1 powerstrip PowerStr1 outlet 1,4,7
CLI Power Strip Configuration
Description: Power Control Menu
Scenario #1 Configure a DSX Port to contain a Power Strip device (the port is
previously connected to a power strip)
Pre-condition Administrator user is logged in via CLI.
Power Strip device (DPX) is physically connected to Port1 of DSX.