Lucent Technologies Release 6 Security Camera User Manual


 
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets
555-230-112
Issue 5
May 1998
Install and Connect Cabinets
Page 1-5Install System Cabinets
1
Model 15A Announcement System See Table 1-1 for PEC codes.
The BLD1 circuit pack provides 8 channels with up to 20 seconds of
recording time on each channel. The BLD2 circuit pack provides 8
channels with up to 40 seconds of recording time on each channel. Each
chassis can be populated with any combination of 2 BLD circuit packs.
The Model 15A Announcement System is FCC registered and does not
require a voice coupler.
2. If earthquake protection is required, skip to ‘‘
Earthquake Protection
Installation’’ on page 1-34.
Install and Position Stratum 3 Clock Cabinet
Check the location of the AC power receptacle. The receptacle must be on a
separately fused circuit that is not controlled by a wall switch. It must be located
within 10 feet (3 m) of the cabinet and should be located outside the MDF area.
1. Position the clock cabinet in the designated location.
2. If earthquake protection is required, skip to ‘‘
Earthquake Protection
Installation’’ on page 1-34.
3. If earthquake protection is not required, level the cabinets and adjust and
lock the cabinet stabilizing bolts to keep the cabinet from moving.
Table 1-1. Model 15A Announcement Equipment
PEC Code Description
PEC 63240 1 chassis and 1 BLD1 circuit pack
PEC 63241 1 BLD1 circuit pack
PEC 63242 1 chassis and 1 BLD2 circuit pack
PEC 63243 1 BLD2 circuit pack
PEC 63246 1 remote record module