Cable Ductwork
Page C-14
C
Install Cross-Aisle to Wall Trough
Refer to Figure C-9 to assemble the ductwork:
1. Install wall mounting bracket to designated location. Hardware to mount
bracket should be determined according to wall type and should be
locally provided.
2. Use thread-forming screws to attach the 3-hole face of the angle bracket
to the I/O trough.
3. Attach the angle bracket to the 6-hole face of the cross-aisle bracket using
three 10-24 X 3/4 inch screws, connected to nuts and washers through the
bottom holes.
4. Attach the I/O cable duct to the cross-aisle bracket using the
thread-forming screws. Attach the other end of the I/O duct to the wall
mounting using 10-24 X 3/4 inch screws, nuts and washers.
Figure C-9. Installation of I/O Cross-Aisle to Wall Trough
Figure Notes
1. Angle Bracket
2. I/O Trough
3. Cross-Aisle Bracket
4. I/O Cable Duct
5. Wall Mounting Bracket
6. Front of Cabinet