Lucent Technologies Release 6 Security Camera User Manual


 
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets
555-230-112
Issue 5
May 1998
Install and Connect Cabinets
Page 1-7Connect AC Power and Ground
1
Tab le 1- 3 describes the power sources and required AC input power.
NOTE:
The type of power required is shown on the cabinet’s rear door.
Table 1-3. AC Power Sources and Plug Type
Power Distribution
Unit Power Sources Power Input
AC power distribution
(J58890CE-1 and
J58890CE-2)
Multi-Carrier Cabinet
Single phase 120 VAC
with neutral
Single phase 240 VAC
with neutral, or single
phase of 3-phase, 208
VAC with neutral
120 VAC, 60 Hz NEMA
5-50R
208/240 VAC, 60 Hz NEMA
L14-30R
AC power distribution
(J58890CH-1)
Multi-Carrier Cabinet
Single Phase 176-264
VAC
200-240 Volts, 50-60 Hz
NEMA L6-30R. Installations
outside the United States
require a receptacle
suitable for use in the
country of installation.